Brazed Plate Heat Exchangers
          E Series

          Progress In Cooling

          The asa E plate heat exchanger is designed for both cooling and heating applications. It is
          commonly used to cool hydraulic fluid and lubricating oil and can be used for water, air, steam
          and gas applications.

          The benefits of asa E plate heat exchangers are:

                strength
                safety
                downsizing
                high thermal efficiency
                low maintenance
                no gaskets – no leaks

          Design

          The asa E plate heat exchanger is designed for maximum heat transfer using profiled plates of acid proof stainless steel. The plates form
          channels through which oil and water pass (alternating every other channel). At the front and back side of the plate package there are cover
          plates. The cooler plates are brazed together at all outer and inner points of contact. The cooler can be installed in charge-pump circuits as well
          as in return lines with high pressure variations.

          Standard Range

          Our standard range of plate heat exchanger covers a large field of applications to ensure you competitive pricing, high quality and short delivery
          times. Contact us for more information and non standard coolers to work out the optimal solution for you.

          Scale Drawing


                                                                       material
                                                                               plates            steel 1.4401
                                                                               upper plate       steel 1.4301
                                                                               connectors        steel 1.4301
                                                                               solder            copper CW004A
                                                                       pressure
                                                                               test pressure     43 bar
                                                                               max. working pressure   30 bar











          Technical Data

          order number   description    A    B    C    D    E     F     G     H     I      J     K    M    weight
                                       [mm]  [mm]  [mm]  [mm]  [mm]          [mm]  [mm]  # of bolts  [mm]  [mm]   [kg]
          ILWPL10014EK   ASA – PL 10-14 E   73   205   64,5   42   172   G ½”   G ½”   27   120   2   -   -   1,8
          ILWPL20020EK   ASA – PL 20-20 E   80   194   82   40   154   G ¾”    G ¾”   27   150   2   -   -   2,3
          ILWPL22030EK   ASA – PL 22-30 E   106   306   109   50   250   G 1”   G ¾”   27   250   4   40   -   6,1
          ILWPL40050EK   ASA – PL 40-50 E   124   304   157   70   250   G 1”   G 1”   27   250   4   75   -   10,2
          ILWPL53020EK   ASA – PL 53-20 E   124   504   85   64   444   G 1”   G 1”   27   450   4   75   -   8,8
          ILWPL53040EK   ASA – PL 53-40 E   124   504   133   64   444   G 1”   G 1”   27   450   4   75   -   13,1
          ILWPL53060EK   ASA – PL 53-60 E   124   504   181   64   444   G 1”   G 1”   27   450   4   75   -   18,4
          ILWPL70060EK   ASA – PL 70-60 E   246   528   182,  174   456   G 1½”  G 1½”   27   420   6   150   210   39,9
                                                   5







          This data sheet shows a technical overview of our products. Please contact us if more exact information is needed. As we are constantly improving our products, their characteristics, dimensions and weights may also change,
          although we do our best to incorporate these changes continually. The information in this data sheet is intended to be used as a first general guideline only. asa assumes no liability for any information therein, any errors, omissions,
          misprints, nor any direct or indirect damages, losses  or costs resulting therefrom. The cooling performance and the general technical values indicated in this catalogue are measured at a test bench according to asa testing
          procedures. Because there is no standardized testing procedure, tests used by other manufacturers could have different results. Due to different conditions in testing and application environments the cooling performance may also
          vary by +/- 15%. Therefore we recommend all coolers to be checked under the system operating conditions. This is also true of vibrations and mechanical stress as well as for pressure peaks and thermal stress and any other
          relevant factors.
                                                      © asa hydraulik, June 2015